Client Protection
Dedicated Support
Dwyer 605-2-WP | Magnehelic® Indicating Transmitter | 0 to 2 inH₂O, Electrical: ± 0.5 %, Mechanical: ± 2 %, 4 to 20 mA
The Dwyer 605-2-WP is a magnehelic® indicating transmitter: differential pressure indicating transmitter, range 0-2.0" w.c. with weatherproof housing.
The Dwyer Series 605 Magnehelic® Differential Pressure Indicating Transmitter is designed for low differential pressure monitoring in building HVAC systems. It provides simultaneous local indication on an analog scale and a standard two-wire, 4-20 mA signal suitable for control applications where visual verification during routine maintenance or troubleshooting is required. The unit measures positive, negative, or differential air and non-combustible, compatible gases.
- Accuracy: Electrical: ± 0.5 %, Mechanical: ± 2 %
- Accuracy Detail: Electrical: ± 4%, Mechanical: ± 4% (includes linearity, hysteresis, repeatability)
- Additional Features 1: Weatherproof Housing
- Compensated Temperature, Max: 48.9 °C
- Compensated Temperature, Min: 0 °C
- Dial Depth: 68 mm
- Specifications
- Features
- Downloads
| Part Number | 605-2-WP |
| Brand | Dwyer |
| Series | 605 |
| Accuracy | Electrical: ± 0.5 %, Mechanical: ± 2 % |
| Electrical Connection | Screw Terminal |
| Supply Voltage | 10 to 35 Vdc |
| Weight | 811 g |
| Accuracy Detail | Electrical: ± 4%, Mechanical: ± 4% (includes linearity, hysteresis, repeatability) |
| Additional Features 1 | Weatherproof Housing |
| Compensated Temperature, Max | 48.9 °C (120 °F) |
| Compensated Temperature, Min | 0 °C (32 °F) |
| Dial Depth | 68 mm (2.68 in) |
| Dial Dia | 4 in |
| Dial Outer Diameter | 127 mm (5.00 in) |
| Electrical Output | 4 to 20 mA |
| Long Term Stability | ± 1% FS/year |
| Loop Resistance | 0 to 1250 Ω max |
| Material Construction Option | Weatherproof Enclosure |
| Measurement Pressure Type | Differential |
| Measurement Pressure, Max | 2 inH₂O |
| Measurement Pressure, Min | 0 inH₂O |
| Mounting Note | Vertical Diaphragm |
| Operating Temperature, Max | 48.9 °C (120 °F) |
| Operating Temperature, Min | -6.67 °C (20 °F) |
| Output Signal | Current |
| Power Consumption | max 38 mA |
| Process Connection Size | 1/8 in |
| Process Connection Type | NPT Female |
| Proof Pressure | Up to 10 psi |
| Span Adjustment | Potentiometers |
| Supply Power Type | DC |
| Thermal Effects | ± 0.045% FS/°C |
| Zero Setting Adjustable Range | Protected Potentiometers |
| Country of Origin | United States |
- Accuracy: Electrical: ± 0.5 %, Mechanical: ± 2 %
- Accuracy Detail: Electrical: ± 4%, Mechanical: ± 4% (includes linearity, hysteresis, repeatability)
- Additional Features 1: Weatherproof Housing
- Compensated Temperature, Max: 48.9 °C
- Compensated Temperature, Min: 0 °C
Other models in this series
Click a row to open that product.
Highlighted values differ from the model you are viewing.
Related Products
Dwyer RSME-C-016-SS | Room Status Monitor | -2 to 2 inH₂O, ± 1 %
Dwyer RSME-C-016-SS | Room Status Monitor | -2 to 2 inH₂O, ± 1 %
Dwyer RSME-C-014-SS | Room Status Monitor | -0.5 to 0.5 inH₂O, ± 1 %
Dwyer RSME-C-014-SS | Room Status Monitor | -0.5 to 0.5 inH₂O, ± 1 %
Dwyer RSME-C-015-SS | Room Status Monitor | -1 to 1 inH₂O, ± 1 %
Dwyer RSME-C-015-SS | Room Status Monitor | -1 to 1 inH₂O, ± 1 %
Dwyer RSME-C-005-SS | Room Status Monitor | 0 to 2 inH₂O, ± 1 %
Dwyer RSME-C-005-SS | Room Status Monitor | 0 to 2 inH₂O, ± 1 %
Dwyer RSME-C-004-SS | Room Status Monitor | 0 to 1 inH₂O, ± 1 %
Dwyer RSME-C-004-SS | Room Status Monitor | 0 to 1 inH₂O, ± 1 %
Dwyer RSME-B-016-SS | Room Status Monitor | -2 to 2 inH₂O, ± 0.5 %
Dwyer RSME-B-016-SS | Room Status Monitor | -2 to 2 inH₂O, ± 0.5 %
Dwyer RSME-B-005-SS | Room Status Monitor | 0 to 2 inH₂O, ± 0.5 %
Dwyer RSME-B-005-SS | Room Status Monitor | 0 to 2 inH₂O, ± 0.5 %
Dwyer RSME-B-015-SS | Room Status Monitor | -1 to 1 inH₂O, ± 0.5 %
Dwyer RSME-B-015-SS | Room Status Monitor | -1 to 1 inH₂O, ± 0.5 %