Client Protection
Dedicated Support
Genuine Products
Dwyer Instruments RHP-2N44 | North American Wall Mount Humidity / Temperature Transmitter with 2% accuracy and universal current / voltage output for RH and Temperature
The most adaptable room transmitter available is the Wall Mount Humidity/Temperature/Dew Point Transmitter, Model RHP-2N44, Series RHP-E/N. To increase measurement accuracy, air flow across the sensor is provided by the attractive housing's well-ventilated design. A fully recoverable capacitive polymer sensor is used to monitor both the dew point and the humidity. While the alternative temperature output can be a current, voltage, RTD, or thermistor, the humidity and dew point can only have a current or voltage output. The temperature range is field adjustable for models where the temperature output is either voltage or current.
- Specifications
- Features
- Downloads
| Accuracy | RH: Model RHP-2XXX +/-2% 10 to 90% RH @ 25°C; Model RHP-3XXX +/-3% 20 to 80% RH @ 25°C; Model RHP-5XXX +/-5% 20 to 80% RH @ 25°C; Thermistor temperature sensor: +/-0.36°F @ 77°F (+/-0.2°C @ 25°C); RTD temperature sensor: DIN Class B; +/-0.54°F @ 32°F (+/-0.3°C @ 0°C); Solid state band gap temperature sensor: +/-0.9°F @ 77°F (+/-0.3°C @ 25°C) |
| Approvals | CE |
| Connection | Electrical: Screw terminal block |
| Display Resolution | RH: 1% Temperature: 0.1°F (0.1°C) Dew Point: 1°F (1°C) |
| Display | Optional LCD Switch selectable %RH or dew point, °F/°C |
| Drift | <.25% RH/year |
| ENCLOSURE MATERIAL | Polycarbonate |
| Enclosure Rating | IP20 |
| Hysteresis | +/-.8% |
| Output Signal | 4-20 mA loop powered outputs: 4-20 mA, 2 channels for humidity/ solid state temperature sensor models (loop powered on RH). Switch selectable RH/dew point. Switch selectable normal or reverse output; 0-5/10V outputs: 5 mA max., 2 channels for humidity/solid state temperature sensor models. Switch selectable 0-10 V/2-10 V or 0-5 V/1-5 V output. Switch selectable RH/dew point. Switch selectable normal or reverse output |
| Power | 4-20 mA loop powered outputs: 10-35 VDC; 0-5/10V outputs: 15-35 VDC or 15-29 VAC |
| Relative Humidity | Range: 0 to 100% RH |
| Repeatability | +/-0.1% typical |
| Response Time | 8 s |
| Sensor Type | Capacitance polymer |
| Temp Range - Operating | -40 to 140°F (-40 to 60°C) |
| Temp Range - Storage | -40 to 176°F (-40 to 80°C) |
| Temperature Range | -40 to 140°F (-40 to 60°C) for thermistor and RTD sensors. -20 to 140°F (-28.9 to 60°C) for solid state band gap temperature sensors |
| Temperature Range | Compensated: -4 to 140°F (-20 to 60°C) |
| Temperature Range | Dew Point: -20 to 140°F (-28.9 to 60°C); 0 to 100°F (-17.8 to 37.8°C); 40 to 90°F (4.4 to 32.3°C); -4 to 140°F (-20 to 60°C) field selectable ranges |
| Type | North American Wall Mount Humidity / Temperature Transmitter |
| Weight | 4.4 oz (125 g) |
- Lower installation costs when temperature, humidity/dew point, and sensing are integrated.
- With a wide range of temperature sensors and 2% and 3% accuracy, there are many application scenarios.
- Inventory was reduced thanks to field-selectable output.
Related Products
Dwyer Instruments RHP-2N40 | North American Wall Mount Humidity Transmitter with 2% accuracy and universal current / voltage output for RH
Dwyer Instruments RHP-2N40 | North American Wall Mount Humidity Transmitter with 2% accuracy and universal current / voltage output for RH
Dwyer Instruments RHRS-10 | 10 plate radiation shield for humidity transmitters
Dwyer Instruments RHRS-10 | 10 plate radiation shield for humidity transmitters
Dwyer Instruments RHRS | 6 plate solar radiation shield for sintered filter version RH transmitters
Dwyer Instruments RHRS | 6 plate solar radiation shield for sintered filter version RH transmitters
Dwyer Instruments RHP-3N4B | North American Wall Mount Humidity / Temperature Transmitter with 3% accuracy and universal current / voltage output for RH and 10K Type II thermistor Temperature Sensor
Dwyer Instruments RHP-3N4B | North American Wall Mount Humidity / Temperature Transmitter with 3% accuracy and universal current / voltage output for RH and 10K Type II thermistor Temperature Sensor
Dwyer Instruments RHP-3N4A | North American Wall Mount Humidity / Temperature Transmitter with 3% accuracy and universal current / voltage output for RH and 10K Type III thermistor Temperature Sensor
Dwyer Instruments RHP-3N4A | North American Wall Mount Humidity / Temperature Transmitter with 3% accuracy and universal current / voltage output for RH and 10K Type III thermistor Temperature Sensor
Dwyer Instruments RHP-3N44-LCD | North American Wall Mount Humidity / Temperature Transmitter with 3% accuracy and universal current / voltage output for RH and Temperature with LCD
Dwyer Instruments RHP-3N44-LCD | North American Wall Mount Humidity / Temperature Transmitter with 3% accuracy and universal current / voltage output for RH and Temperature with LCD
Dwyer Instruments RHP-3N44 | North American Wall Mount Humidity / Temperature Transmitter with 3% accuracy and universal current / voltage output for RH and Temperature
Dwyer Instruments RHP-3N44 | North American Wall Mount Humidity / Temperature Transmitter with 3% accuracy and universal current / voltage output for RH and Temperature
Dwyer Instruments RHP-3N40-LCD | North American Wall Mount Humidity Transmitter with 3% accuracy and universal current / voltage output for RH with LCD
Dwyer Instruments RHP-3N40-LCD | North American Wall Mount Humidity Transmitter with 3% accuracy and universal current / voltage output for RH with LCD