Genuine Dwyer Instruments CMT200-R carbon monoxide transmitter, in stock at General Tech Services LLC, UAE. This 0-200 ppm CO transmitter provides a jumper-selectable 4-20 mA or 2-10 V output and uses a field-replaceable electrochemical sensor in a rectangular UV-resistant polycarbonate enclosure. Free UAE-wide shipping. Request a quote in under a minute - call +971 6 5436933.

Product Overview

The Dwyer CMT200-R is a carbon monoxide transmitter designed for monitoring CO concentrations in underground parking garages, vehicle maintenance facilities, mechanical rooms and other ventilation applications.

The transmitter measures carbon monoxide from 0 to 200 ppm and provides a field-selectable output of either 4-20 mA or 2-10 V. The output is selected using an internal jumper, allowing the transmitter to interface with a wide range of building automation and control systems.

The CMT200-R uses a field-replaceable electrochemical sensor with a typical lifespan of 4 years. It provides a typical coverage area of 5,000 to 7,000 ft², depending on the application and installation conditions.

Field calibration is performed using the 15-turn zero and span potentiometers together with the A-507A calibration adapter and GCK-200CO-2000CO2 calibration gas when required. The rectangular enclosure is made from UV-resistant polycarbonate and includes removable terminal blocks with PG11 and PG16 conduit knockouts.

The CMT200-R is the standard version. The CMT200-R-FC version has the same core specification and additionally includes a factory calibration certificate.

Key Benefits

  • 0-200 ppm carbon monoxide measurement range
  • Jumper-selectable 4-20 mA or 2-10 V output
  • Field-replaceable electrochemical sensor with approximately 4-year typical lifespan
  • 15-turn zero and span potentiometers for field calibration
  • Typical coverage of 5,000 to 7,000 ft²
  • Rectangular UV-resistant polycarbonate enclosure
  • Suitable for BAS and building automation CO monitoring
  • Field calibration capability using the appropriate calibration accessories
  • Free UAE-wide shipping on genuine Dwyer Instruments stock

Who This Product Is Best For

  • Underground parking garages requiring CO monitoring for ventilation control
  • Loading docks and similar areas requiring carbon monoxide monitoring
  • Vehicle maintenance facilities requiring continuous CO monitoring
  • Mechanical rooms using carbon monoxide monitoring in building automation systems
  • Building automation and control integrators requiring selectable analog outputs

How to Specify & Commission It

  1. Confirm the required 0-200 ppm CO measurement range and select a suitable mounting location within the monitored area.
  2. Install the transmitter according to the manufacturer's installation requirements, considering the typical 5,000-7,000 ft² coverage guidance.
  3. Set the output jumper for either 4-20 mA or 2-10 V according to the connected controller or BAS input.
  4. Connect the 18-28 V supply and selected output to the controller using the removable terminal block.
  5. If required, perform field calibration using the 15-turn zero and span potentiometers, A-507A calibration adapter and GCK-200CO-2000CO2 calibration gas.
  6. Verify the CO reading and output signal with the connected control or building automation system.

Frequently Asked Questions

What range does the CMT200-R measure?

The transmitter measures carbon monoxide from 0 to 200 ppm.

What outputs does the CMT200-R provide?

It provides a jumper-selectable 4-20 mA loop-powered output or 2-10 V output.

How long does the sensor typically last?

The field-replaceable electrochemical sensor has a typical lifespan of approximately 4 years, depending on operating conditions and application.

What is the typical coverage area?

The CMT200-R provides a typical coverage area of 5,000 to 7,000 ft², depending on the installation and monitored environment.

What is the accuracy of the CMT200-R?

The specified accuracy is ±2% of reading at the time of calibration.

Can the sensor be replaced?

Yes. The CMT200-R uses a field-replaceable electrochemical carbon monoxide sensor.

How is the transmitter calibrated?

Field calibration is performed using the 15-turn zero and span potentiometers, together with the A-507A calibration adapter and appropriate calibration gas.

Is a factory calibration certificate available?

Yes. The CMT200-R-FC version includes a factory calibration certificate. The standard CMT200-R does not.

Is genuine CMT200-R stock available with UAE shipping?

Yes. Genuine Dwyer Instruments stock is available through General Tech Services LLC, UAE, with free UAE-wide shipping. Call +971 6 5436933 for pricing and current availability.

Request a Quote Today

For pricing, stock availability or to place an order, contact General Tech Services LLC.

Call +971 6 5436933 | www.generaltechshop.ae


 

Availability: in stock
Free Saudi Arabia shipping available
For pricing, please contact our experts.